CBCA 7039
Board: CBCA
Agency: Department of Veterans Affairs
Appellant: Hamilton Pacific Chamberlain
Date: 2021-07-07
Outcome: granted
GRANTED: July 7, 2021
CBCA 7039
HAMILTON PACIFIC CHAMBERLAIN,
Appellant,
v.
DEPARTMENT OF VETERANS AFFAIRS,
Respondent.
P. Sean Milani-nia and Rachel M. Severance of Fox Rothschild LLP, Washington,
DC, counsel for Appellant.
Nathan Menard, Office of General Counsel, Department of Veterans Affairs,
Washington, DC, counsel for Respondent.
CHADWICK, Board Judge.
The Board handled this appeal under the small claims procedure of Board Rule 52 (48
CFR 6101.52 (2020)). The parties submitted the case on the record under Rule 19 and filed
two rounds of briefs. This “decision is final and conclusive, shall not be set aside except for
fraud, and is not precedential.” Rule 52(c); see 41 U.S.C. § 7106(b)(4), (5) (2018).
“Because we write for the parties, we include only minimal background for context.”
Diamond v. Shulkin, 692 Fed. App’x 637, 637 (Fed. Cir. 2017); see Rule 52(c) (“The
presiding judge may issue a decision in summary form.”). The contractor’s October 2020
administrative claim alleged that the contracting officer’s direction to demolish and rebuild
a concrete pad for an exterior storage building was a constructive change that cost
$41,809.87 to perform. The contractor (HPC) appealed a deemed denial of the claim and
elected the small claims procedure without objection by the agency (VA).
CBCA 7039 2
HPC originally poured the pad sloped from an elevation of 98.65 feet at the internal
edge of the pad down to 98.50 feet at the landscape side. HPC argues that “the civil
drawings provided detailed elevations for the Storage Pad” and depicted the slope, whereas
“the architectural drawings only provide[d] the overall storage building elevation.” VA
responds that “at least six” architectural and structural “drawings clearly show that the
concrete slab was to be constructed at a flat grade” and that HPC misreads civil drawing
C2.02, on which HPC relies. (VA admits, however, that after the dispute about the slope
arose, VA agreed to have HPC rebuild the pad sloping inward toward the adjacent building.)
The dispute centers on the parties’ interpretations of the two spot elevations of 98.50
feet shown in civil drawing C2.02 in crosshair symbols next to, but slightly outside of, the
outside corners of the pad. VA argues that those spot elevations show the landscape grade
next to the pad, where the crosshairs aim. Alternatively, VA argues that the elevations were
at least ambiguous, such that HPC should have sought clarification before proceeding. HPC
responds that its “interpretation of C2.02” as depicting a sloped pad “is the only reasonable
interpretation” and that “VA’s contention that the back wall of the storage structure is the
only structural element in the entire drawing without proposed spot elevations and
simultaneously is the only location in any contract drawing with proposed spot elevations
in the landscape, does not withstand scrutiny.” HPC argues that the positioning of the
crosshairs slightly in the landscape is an obvious computer-aided drawing glitch.
We read the civil drawing as HPC does. Contract documents can be clear even if
parsing them requires close attention. E.g., Bank of America, National Ass’n v. Department
of Housing & Urban Development, CBCA 5571, 18-1 BCA ¶ 36,927 (2017) (citing McCann
v. McGlynn Lumber Co., 34 S.E.2d 839, 845 (Ga. 1945)). The decisive consideration here
is that proposed spot elevations are shown in the “C2” grading drawings either at or near
structural edges or on top of ground contour lines; we see no indicia that a spot elevation for
construction would sit alone in the landscape unconnected to another drawing element. To
the contrary, when we asked for examples of proposed spot elevations used in combination
with contour lines to show landscape grading, VA cited only examples where the crosshairs
aim directly at contour lines. The crosshairs are supposed to aim at a line. In most instances,
they do. Where they do not, they almost do. The natural interpretation of the spot elevations
next to the outer corners of the pad in drawing C2.02 is as elevations of the adjacent drawing
element, the pad. Otherwise, as HPC notes, this area of the drawing would be the only area
where structural corners had no spot elevations and proposed spot elevations had no referent
lines.